DESCRIPTION
The NC706 Fire Panel Interface (FPI) is designed to deactivate all NC704 Maglocks and NC705 Elevator Deactivation Panels in the event of a fire alarm or loss of fire panel functionality. Audio and visual alerts on the TekCARE®700 system remain operational while door restraints are disabled.
Each NC706 FPI is capable of interfacing with up to eight NC702 Door Controllers.
The NC706 Fire Panel Interface requires a normally closed contact from the facility’s Fire Alarm Control Panel that goes open when a fire alarm is sounded. The contact must also open if the fire panel becomes inoperable.
The Reset button on the front of the housing is used to re-enable any connected NC704 Maglocks and NC705 Elevator Deactivation Units once the fire alarm has been cleared. If desired, this reset button may be replaced with a jumper to provide automatic reset once the fire alarm has been cleared.
The NC706 is powered by a PK505 12 VDC Power Supply
SPECIFICATIONS
- Size: 6.29" × 5.68" × 2.00"
- Weight: 1.6 lbs
- Construction: Powder Coated Steel
- Operating Voltage: 12 VDC
- Current Draw: 120 mA maximum
- Contact Rating: 2A/24 VDC
- Mounting: Surface